■ DC circuit monitoring of over- and undervoltage
■ Adjustable over- and undervoltage threshold
■ Adjustable trip delay time
■ Powered by the measuring circuit
■ 1 C/O contact
■ 2 LEDs for status indication
Type
|
DVM-A
|
Measuring circuit
|
DC circuit
|
Rated voltage
|
DC12V,DC24V,DC36V,DC48V
|
Monitoring functions
|
overvoltage, undervoltage
|
Voltage setting range
|
Rated voltage
|
Undervoltage
|
Vvervoltage
|
DC12V
|
10-14V
|
13-17V
|
DC24V
|
20-28V
|
26-34V
|
DC36V
|
30-42V
|
39-51V
|
DC48V
|
40-56V
|
52-68V
|
|
Trip delay time
|
1-10s adjustable
|
Indicators
|
Normai, Trip
|
Output contacts
|
1 C/O
|
Contact capacity
|
3A 250VAC
|
Dimensions (H×W×D)
|
50×40×57.5mm
|
Mounting
|
DIN rail
|
|