■ Built-in LCD and keypad afford a precise,digital setting
■ Three-phase monitoring of phase sequence, phase loss, over- and undervoltage
■ Adjustable over- and undervoltage threshold
■ Independent adjustable delay time for phase sequence, phase loss, overvoltage, undervoltage
■ Powered by the measuring circuit
■ 1 C/O & 1NC contacts
■ with Timing, counting and faulure recording
Type
|
JVR800-1
|
Measuring circuit
|
L1,L2,L3
|
Rated voltage
|
380VAC,50/60Hz
|
Monitoring functions
|
phase sequence, phase loss, overvolatege, undervoltage, timing, counting
|
Overvoltage setting range
|
380-600V
|
Undervoltage setting range
|
100-380V
|
Hysteresis
|
1-20V
|
Delay time for overvoltage and undervoltage
|
1-20s
|
Delay time for phase loss
|
1-20s
|
Delay time for phase sequence
|
1-20s
|
Indicators
|
LCD indicating voltage,current,operation status
|
Output contacts
|
1 C/O,1NC
|
Contact capacity
|
6A 250VAC
|
Dimensions (H×W×D)
|
80×43×54mm
|
Mounting
|
DIN rail
|
|